Can be used for emergency stop or guard door applications
Basic unit in accordance with EN 60204-1 and EN 954-1 for one or two-channel emergency stop monitoring
Safety category 4 pursuant to EN 954-1
Stop category 0 pursuant to EN 60204-1
Manual or automatic start
With / without cross circuit detection
Control loop for monitoring external contactors
3 enabling paths, N/O force guided
For processing signals of a light grid (OSSD compatible) pursuant to DIN EN 61496-1
LED displays for operating voltage, channel 1 and channel 2
Enclosure width 22.5 mm
Supply current circuit | |
Nominal voltage UN: | 24 VAC / DC or 230 VAC |
Nominal frequency: | 50 → 60 Hz |
Operating voltage range: | 0.85 → 1.1 x UN |
Control circuit | |
Response time tA1 (S34): | 20 → 40 ms |
Response time tA2 (S35): | 200 → 600 ms |
Fallback time tR (K1, K2): | <25 ms |
Output circuit | |
Contact assignment: | 3 NO |
Contact type: | Force guided |
Nominal switching voltage Un: | 240 VAC / 300 VDC |
Max. Continuous current In per current path: | 6A |
Max. total current of all current paths: | 12 A (at 24 V) / 8 A (at 230 V) |
Mechanical lifespan: | 10 x 106 |
General data | |
Connection type: | Screw terminals |
Protection rating enclosure / terminals: | IP40 / IP20 |
Dimensions (H x W x D): | 96.5 x 22.5 x 114 mm |
Weight: | 210 g |
Ambient temperature: | -25 °C → +55 °C |
CE, BG, GS, UL, CSA, CCC
EN 954-1, EN 60204-1, EN 61496-1