Level monitoring and control of conductive liquids and powders, e.g. maximum and minimum fill level, protection against overfilling and dry running
Monitoring and control of the mix ratio for conductive liquids
General resistance monitoring, e.g. recording temperature limits with PTC (device to IEG 255, VDE 0435 section 303)
3 electrode connections for 2-point and 1-point level control
The metering circuit galvanically isolated from the mains is immune from high levels of interference
Max. lead length to the electrodes: 1500 m
Wide setting range: 2 → 450 kΩ which enables differentiation between liquid and foam
Adjustable response and fallback delay: 0.2 → 20 s
Programmable for working current principle (without bridge) or rest current principle (X1-X2 and/or X1-COM bridge)
2 LEDs to indicate operating readiness and contact position
1 changer
Overall width 22.5 mm, protection class IP40
Input | |
Liquid resistance | 2 → 450 kΩ adjustable |
Switch point hysteresis | approx. 3% (at 450 kΩ) |
approx. 6% (at 2 kΩ) | |
Max. Cable length to the electrodes | 450 kΩ / 50 m |
Set value/cable length | 100 kΩ / 200 m |
35 kΩ / 500 m | |
10 kΩ / 1500 m | |
5 kΩ / 3000 m | |
Max. Electrode voltage/current (internally produced) | approx. AC 10 V / approx. AC 1.5 mA |
Auxiliary voltage UH | AC 220-240 V, 45 / 400 Hz |
or DC 24 V | |
Auxiliary voltage range | 0.85 → 1.1 UH |
Output | |
1 changeover | |
Thermal current | 5 A |
Switching capacity | AC11: 3A / AC 230 V |